Products

Previous product   Next product

FSD-111-2 Series - 1 1/2 Hour Fire and Smoke Damper

Standard Features

  • Class 2 (Low Leakage) standard
  • Right hand mount standard
  • Bi-directional damper for horizontal or vertical installation
  • Vertical damper is for horizontal duct (wall installation)
  • Horizontal damper is for vertical duct (floor installation)
  • UL and California State Fire Marshall approved
  • Parallel blade operation
  • Power open / spring closure
  • 16 gauge galvanized steel channel frame
  • 16 gauge galvanized triple "V" formed blades
  • Sintered bronze, oil impregnated bearings
  • Axles: 1/2" square zinc plated steel studs
  • Linkage: .12 x .50 zinc plated steel concealed in the channel frame
  • Jackshaft: 1/2" diameter zinc plated steel with jackshaft connector coupling
  • Caulking, UL approved silicone sealants: Dow Corning RTV-732, 999A, GE-1200
  • Blade Seals: 60-65 Durometer Silicone rubber with laminated acrylic adhesive permanently bonded to blade edges
  • Jamb Seals: Corrosion resistant stainless steel
  • Minimum size: 8w x 8h
  • Maximum single section: 36w x 36h
  • R Stat - Resettable reusable thermal disc, fixed setting of 165°, replaces the fusible link
  • Standard sleeve (type A) 20 gauge, 18" minimum
  • Standard actuator 120v mounted in "right/front" position

Options

  • FSD-111-1 - Class 1 Ultra Low Leakage (minimum size 12w x 8h, maximum size 36w x 36h)
  • Smoke ONLY damper
  • SD-333-1 - Class 1 smoke ONLY damper (minimum size 12w x 8h, maximum size 36w x 36h)
  • SD-333-2 - Class 2 smoke ONLY damper (minimum size 8w x 8h, maximum size 36w x 36h)
  • 24v actuator
  • Pneumatic actuator
  • Internal mount actuator (mimum damper 8x8", minimum 18" sleeve)
  • 165° fusible link
  • Retaining angles see "Engineering and Performance Data" on the following product
  • Fire/Smoke Damper Optional Sleeve Styles
  • Optional sleeve lengths and/or gauge
  • Optional access door mounted in sleeve
  • DH100ACDC - factory installed duct smoke detector (minimum 20" or 25" sleeve required)
  • Stainless steel contstruction

Installation Instructions